LCLeftFrame1

Laboratory Services

Control Limit Parameter for testing for various Systems

SYSTEM à

PARAMETERS

Closed Loop System

Cooling Tower

Hard Water Steam Boiler

Soft Water Steam Boiler

Test

Limit

Test

Limit

Test

Limit

Test

Limit

Total Hardness (Mg2+ & Ca2+)

4

#

4

#

4

#

4

#

pH ( -log[H+] )

4

7.5 – 9.5

4

7.5 – 9.5

P Alkalinity

4

200 - 400

4

200 - 500

4

425 - 850

4

425 – 850

Total Alkalinity

4

< 400

4

< 500

4

< 850

4

< 850

Bi-Carbonate Alkalinity (HCO3=)

CALC

CALC

CALC

CALC

Carbonate Alkalinity (CO3=)

CALC

CALC

CALC

CALC

Hydroxide Alkalinity (OH-)

CALC

CALC

CALC

CALC

TDS (Total Dissolved Solids)

4

< 1500

4

< 1500

4

2000 - 3000

4

2000 – 3000

Phosphonates (Organic)

4

#

Chloride (Cl-)

4

#

4

#

Sulphite (SO3=)

4

20 - 60

4

20 – 60

Condensate pH

4

7.5 – 8.5

4

7.5 – 8.5

Phosphate (PO43-)

4

Softener Hardness

4

< 2

Silica (Si)

4

< 30

4

< 30

4

< 25

Iron (Fe)

4

< 0.1

4

< 0.1

4

< 0.2

4

< 0.2

4           :           Testing of Control Parameter should be included for a treated system

#          :           Value are to be compared with treatment control parameters.

CALC     :           Calculated value.

 

Bi-Carbonate Alkalinity, Carbonate Alkalinity & Hydroxide Alkalinity à Calculate from P Alkalinity & Total Alkalinity

 